Delta AH500 — 2.2.14 Special Data Registers

Chapter 2 Devices 2-69 CPU5×0-RS2 CPU5×0-EN CPU5×1-RS2 CPU5×1-EN Attribute Default OFF STOP RUN SR Function    ON RUN STOP by the instruction IMASK. SR636 Bit 0~bit 15: The conditions of the interrupt programs I208~I213 are set by the instruction IMASK. ○ ○ ○ ○ FFFF – – R FFFF SR637 Bit 0~bit 15: The conditions of the interrupt programs I214~I229 are set by the instruction IMASK. ○ ○ ○ ○ FFFF – – R FFFF SR638 Bit 0~bit 15: The conditions of the interrupt programs I230~I255 are set by the instruction IMASK.

○ ○ ○ ○ FFFF – – R FFFF *SR655 ↓ SR662 Recording the mapping error occurring in the module table for rack 1 or the error occurring in the I/○ module of rack 1 ↓ Recording the mapping error occurring in the module table for rack 8 or the error occurring in the I/○ module of rack 8 ○ ○ ○ ○ 0 – – R 0 *SR663 ↓ SR674 Recording the mapping error code occurring in the module table for rack 1 whose slot number is 0 ↓ Recording the mapping error code occurring in the module table for rack 1 whose slot number is 11 ○ ○ ○ ○ 0 – – R 0 *SR675 ↓ SR682 Recording the mapping error code occurring in the module table for rack 2 whose slot number is 0 ↓ Recording the mapping error code occurring in the module table for rack 2 whose slot number is 7 ○ ○ ○ ○ 0 – – R 0 *SR683 ↓ SR690 Recording the mapping error code occurring in the module table for rack 3 whose slot number is 0 ↓ Recording the mapping error code occurring in the module table for rack 3 whose slot number is 7 ○ ○ ○ ○ 0 – – R 0 *SR691 ↓ SR698 Recording the mapping error code occurring in the module table for rack 4 whose slot number is 0 ↓ Recording the mapping error code occurring in the module table for rack 4 whose slot number is 7 ○ ○ ○ ○ 0 – – R 0