Delta Electronics — 6.27.2 Explanation of CANopen Communication Instructions

Chapter 6 Applied Instructions 6.27.2 Explanation of CANopen Communication Instructions Symbol S : Number of station to be initialized Explanation 1. Before executing the instruction, be sure to select Delta Special Driver & AS Remote Mode as the working mode 6_ for function card 2 in the hardware configuration software (HWCONFIG) in ISPSoft. 2. The servo range of S is 1–8. When the input value is greater than 8, PLC will automatically process 8 as the value of S for the initialization. The station address must start at 1 and the following addresses cannot be skipped or reserved. 3. When the PLC firmware is V1.02.00 or later, S ranging from 21 to 28 is added for inverters.

For the input value that is not in the range of 21 to 28, this instruction will not be executed. Same rule applies to the servo; the station address must start at 21 and the following address should be in consecutive order. 4. When setting the number of station to be initialized to 5, this instruction initializes station address from 1 to 5. And when setting the number of station to be initialized to 23, this instruction initializes station address from 21 to 23. When there are 5 servo systems and 3 inverters that need to be initialized, you need to execute this instruction twice. One is INITC 5 for 5 servo systems and the other is INITC 23 for 3 inverters. 5.

SM1681 is set to OFF when you execute this instruction on servos ( S is 1–8). SM1681 is set to ON when the initializations are complete. SM1683 is set to OFF when you execute this instruction on inverters ( S is 21–28). SM1683 is set to ON when the initializations are complete. 6-893 API Instruction Operand Description 2800 INITC S Initializing the servo for CANopen communication Device X Y M S T C HC D FR SM SR E K 16# “$” F S   BOOL WORD DWORD LWORD UINT INT DINT LINT REAL LREAL TMR CNT STRING Data type S  Pulse Instruction 16-bit instruction 32-bit instruction - AS -