Chapter 6 Applied Instructions Symbol Node : Specified node ID 6_ Dest : Target device for storing data Len : Total number of 4 words of data which have been read Ok : Completion flag Err : Error flag Explanation 1. The EMER instruction is applicable to CANOpen DS301 mode and Delta special mode. 2. Only the PLC firmware of V1.04.10 and later can support the instruction. 3. After receiving the Emergency message from the slave Node , the PLC will automatically store the data in the specified storage device and set the Ok flag to ON. 4. It is recommended that the Node value should be specified from the slave node IDs which have already existed.
If the value is not one existing node ID or the slave has been disconnected, the PLC will not be able to receive any message, set the Err flag to ON and show error code of communication timeout. (Refer to explanation of SR659 for error codes.) 6-933 API Instruction Operand Description 2811 EMER Node,Dest,Len,Ok,Err Reading Emergency message Device X Y M S T C HC D FR SM SR E K 16# “$” F Node Dest Len Ok Err BOOL WORD DWORD LWORD UINT INT DINT LINT REAL LREAL TMR CNT STRING Data type Node Dest Len Ok Err Pulse Instruction 16-bit instruction 32-bit instruction - AS -