Delta Electronics — 7.2.6 BAT. LOW LED Indicators Blinking Every 0.5 Seconds

Chapter 7 Troubleshooting 7.2.3 ERROR LED Indicators Blinking Rapidly Every 0.2 Seconds This happens when the power supply 24 VDC of the CPU module is disconnected, or the power supply is not sufficient, not stable or abnormal. 7.2.4 ERROR LED Indicators Slow Blinking Every 3 Seconds and Lighting up for 1 Second 7.2.5 BAT. LOW LED Indicators Are ON This happens when there is no battery (CR1620) or the power is low. Turn this option off in the HWCONFIG > CPU > Device Setting > Show Battery Low Voltage Error CPU when you don’t need the RTC function to keep track of the current 7_ time (default is enabled). 7.2.6 BAT.

LOW LED Indicators Blinking Every 0.5 Seconds This happens when RTC cannot keep track of the current time. 7-7 Error Code Description Solution Flag Log (16#) 002A The external voltage is abnormal. Check whether the external 24 V power supply to the module is normal. SM7 V Error Code Description Solution Flag Log (16#) 1500 Connection lost in the remote modules Check the network connection cable. SM30 V 1502 - 150F Errors occurred in the remote modules Refer to Section 7.3.4 for more information on the remote module error codes. SM30 V 1800 - 180F Errors occurred in the extension modules Refer to Section 7.3 for more information on the extension module error codes.

SM10 V 1900 - 191C Heartbeat errors occurred in the slave of the CANopen communication module. 1. Check the CANopen connection cable. 2. Check if the specific slave is working properly. Note: The last 2 digits of the error code represent the ID number of the slave (convert hexadecimal to decimal). - V Error Code Description Solution Flag Log (16#) 0027 Battery Low Change battery or turn this option off SM219 X Error Code Description Solution Flag Log (16#) RTC cannot keep track of the 0026 Contact your distributor. SM218 V current time