Chapter 7 Troubleshooting 7_ 7-9 005D The CPU module does not detect a memory card. Check that the memory card is inserted correctly into the CPU module. SM453 V 005E The memory card is initialized incorrectly. Check whether the memory card is broken. SM453 V 0063 An error occurs when data is written to the memory card. Check whether the file path is correct or whether the memory card is malfunctioning. SM453 V 0064 A file in the memory card cannot be read. Check whether the file path is correct, or whether the file is damaged. SM453 V 1950 The initialization of t CANopen communication module has not yet been completed, the CANopen instructions cannot be executed. 1.
Check the CANopen connection cable. 2. Check if the specific slave is working properly. 3. If nothing is wrong, initialize the CANopen communication module again. - V 2001 Not using the FCOMP card or not in the right mode for the ASDA-A2 while using the CANopen communication instruction. Use the FCOMP card in the function card slot to check if the operation mode is correct. SM0 V 2003 The device used in the program exceeds the device range or it is illegal. Check the program, compile the program again, and download the program again. SM0 V 200B The operand n or the other constant operands K/H exceed the range. Check the program, compile the program again, and download the program again.
SM0 V 200C The operands overlap. Check the program, compile the program again, and download the program again. SM0 V 200D The binary to binary-coded decimal conversion is incorrect. Check the program, compile the program again, and download the program again. SM0 V 200E The string does not end with 00. Check the program, compile the program again, and download the program again. SM0 V 2012 Incorrect division operation Check the program, compile the program again, and download the program again. SM0 V 2013 The value exceeds the range of values that can be represented by the floating-point numbers. Check the program, compile the program again, and download the program again.
SM0 V 2014 The task designated by the TKON or YKOFF instruction is incorrect or exceeds the range. Check the program, compile the program again, and download the program again. SM0 V 2017 The instruction BREAK is written outside of the FOR-NEXT loop. Check the program, compile the program again, and download the program again. SM0 V 2027 No such position planning table number or the format is incorrect. 1. Check the program, compile the program again, and download the program again. 2. Check the settings of the position planning table. SM0 V 2028 High speed output instruction is being executed. Only one instruction can be executed at a time.
Refer to SR28 for the record of the axis number and rearrange the output control procedures. - V 2030 The output frequency executed by CSFO instruction exceeds the maximum output frequency. Modify the ratio of input and output frequency or lower the input frequency. - V 2031 If the input pulse is 0 Hz and lasts for more than 2 seconds, PLC stops outputting automatically. Modify the ratio of input and output frequency or lower the input frequency. - V 6004 The IP address filter is set incorrectly. Set the Ethernet parameter for the CPU module in HWCONFIG again. SM1108 X 600D RJ45 port is not connected. Check the connection. SM1100 X