Delta Electronics — 6.17.2 Explanation of Real-time Clock Instructions

Chapter 6 Applied Instructions D100=K2, indicating DST state is being read. Enable contact M1 Setting values and descriptions: Use the instruction DST or HWCONFIG in ISPSoft to read the daylight saving state. The HWCONFIG converts the result from week number to the corresponding dates and months automatically. Enable the contact M0 OFF=>ON again; this act has no impact on the DST. The DST does not reset. Setting values and descriptions: 6_ If the daylight saving time starts from 3 o’clock of 1 st April, 60 minutes is added; the real-time clock shows 4 o’clock of 1 st April.

No matter how many times the contact M0 is disabled or enabled, the real-time clock keeps the same daylight saving time. 6-515 Device Setting Description Value D100 2 Before firmware V1.04 (V1.04 excluded), function code is fixed to 2, indicating the DST state is being read. 5 After firmware V1.04 (V1.04 included), function code is 5, indicating the DST state is ON and in mode 1. D101 4 Starting month: April D102 1 Starting date: the 1st D111 9 Ending month: September D112 3 Ending date: the 3rd D120 60 Duration: 60 minutes Y0.1 ON Node state is ON.

Device Setting Description Value D100 2 Before firmware V1.04 (V1.04 excluded), function code is fixed to 2, indicating the DST state is being read. 5 After firmware V1.04 (V1.04 included), function code is 5, indicating the DST state is ON and in mode 1. D101 4 Starting month: April D102 1 Starting date: the 1st D111 9 Ending month: September D112 3 Ending date: the 3rd D120 60 Duration: 60 minutes Y0.1 ON Node state is ON.