Chapter 6 Applied Instructions Symbol S 1 : Communication port number S 2 : VFD station address 6_ S 3 : Function code S : Source and received data Explanation 1. S 1 sets the communication port number. The number for COM1 is 1, COM2 is 2, Card1 is 11 and Card2 is 12. If the value exceeds the valid range, the instruction does not receive any communication data. 2. S 2 sets the station address for the VFD AC motor drive. 0 indicates that the instruction uses the broadcast mode. The range is between 0–254, and the instruction is not executed if this value is out of the valid range. 3.
S 3 is the communication function code, and S is the source or received data as explained in the following table. 6-583 API Instruction code Operand Function 1814 VFDRW S1, S2, S3, S Serial communication instruction exclusive for Delta AC motor drive Device X Y M S T C HC D FR SM SR E K 16# “$” F S1 S2 S3 S BOOL WORD DWORD LWORD UINT INT DINT LINT REAL LREAL TMR CNT STRING Data type S1 S2 S3 S Pulse instruction 16-bit instruction 32-bit instruction - AS - S3 S3 function name S source and received data Remark function code 0 Reset due to abnormality Unused Any value can be stored in S.