AS Series Programming Manual 6.20.2 Explanation of Other Instructions Symbol Explanation 1. This instruction resets the watchdog timer to monitor the operation of the AS Series PLC system. 2. If the program scanning time in the PLC exceeds 200 milliseconds, the error LED indicator is ON, and the PLC stops running. 3. The watchdog timer acts in the following cases. The system is behaving abnormally. Program execution takes too much time, and therefore the scan time is longer than the watchdog timer setting value. There are two way you can improve the situation. _6 (a) Use the WDT instruction to reset the watchdog timer.
STEP0 END WDT t1 t2 (a) Refer to the ISPSoft User Manual for more information about changing the watchdog timer setting value. 6-630 API Instruction code Operand Function 1900 WDT P ─ Watchdog timer Pulse instruction 16-bit instruction 32-bit instruction AS AS ─