Delta Electronics — 6.21.2 Explanation of String Processing Instructions

AS Series Programming Manual The merged result: D0~D7= “abcd,1234,5.67;”; the quantity of merged strings: D100=15. Additional remarks 1. If the string in S 1 does not end with 16#00, SM0 is ON, and the error code in SR0 is 16#200E. 2. If the string in S 2 does not end with 16#00, SM0 is ON, and the error code in SR0 is 16#200E. 3. If D 1 + ( D 2 +1)/2 – 1 exceeds the device range, the instruction is not executed, SM0 is ON, and the error code in SR0 is 16#2003. 4. Ending character 16#00 or 16#0000 will be added behind the merged string. See the examples above.

_6 6-704 Device D0 D1 D2 D3 D4 D5 D6 D7 HEX 6261 6463 312C 3332 2C34 2E35 3736 003B String “ba” “dc” “1,” “32” “,4” “.5” “76” Upper 8-byte: 16#00 ; lower 8-byte: “;”