Komatsu — 3.17.4 INDICATION OF OPERATIONAL MODES AT CONTROL MODULE, AFTER AUTOMATIC ACTUATION OF THE FIRE S...

OPERATION 3.17 FIRE DETECTION AND SUPPRESSION SYSTEM 3.17.4 INDICATION OF OPERATIONAL MODES AT CONTROL MODULE, AFTER AUTOMATIC ACTUATION OF THE FIRE SUPPRESSION SYSTEM Alarm to Shutdown Period - The RED alarm LED and the audio alarm will pulse at a rate of 2 times per second. Shutdown to Discharge Period - The RED alarm LED and the audio alarm pulses "on" four times per second. Timer Setting (factory adjustment) G Alarm to Shutdown: 5 seconds G Shutdown to Discharge: 10 seconds In Case of Fire G Act according to the circumstances and the applying safety regulations.

G Evacuate area to lessen risk of injury from flames, heat, hazardous vapours, explosions, or other hazards that may be created. G Evacuate endangered Persons. G Inform the fire brigade. G Fight the fire. For continued protection, the Detection and Actuation Sys- tem and the Fire Suppression System must be recharged through authorized Service Personnel immediately after operation. 253 WARNING CAUTION