eng — 12.7 PRECAUTIONS FOR OPERATING

12. OPERATION 12.7.3 CABLE SELECTING Cable thickness lf the load current flowing through the cable exceeds the permitted current, it will cause burning out because of excess heat. If the cable is too thin for the length, the input voltage of the electrical equipment will drop, and this may reduce the production or prevent aS T Load current | (A) S (mm’*) the machine from working. The drop in the voltage from the current used and the thickness and length of the cable can be calculated by the following formula. Drop in voltage e (V) 1 x 58 length L (m) thickness S (mm) * currentI(A) x V3 Select the length and thickness of the cable so that the drop in the voltage is within 5%.

The relationship between the current used and the thickness, length, and permissible current in the insulated cable (single core and triple core) is as shown in the table below. (Note: The voltage used is taken as 200 V and drop in voltage as 10 V.) Single core (Unit: mm?) Length(m) |Less than| Curren 50m 555, | 100m | 125m | 150m | 200m 50A 8 14 22 22 30 38 100A 22 30 38 50 50 60 200A 60 60 60 80 100 125 300A 100 100 100 125 150 200 Triple core (Unit: mm?) Length(m) jLess50mthan} Curren 2-40 555, | 199m | 125m | 150m | 200m 50A 14 14 22 22 30 38 100A 38 38 38 50 50 60 38x22 | 50x2 50 x 2 60 x 2 200A 38x2 | 38x2 300A 60 x 2 60 x 2 60x2 | 60x2 | 80x2 | 100x2 (m) AE704398