eng — 12.7 PRECAUTIONS FOR OPERATING

12. OPERATION 12.7.4 HANDLING ELECTRICAL (EG125BS-2) LEAKAGE RELAY A WARNING e Always connect the load end to the ground. If it is not grounded, there is danger that the electricity will flow through your body. This relay does not work for electrical leakage when the load is at the 100V/110V end, so always carry out grounding of the outer box (Type 3 grounding) of the load equipment. e Always carry out individual grounding for the electrical leak- Ne sel ny age relay grounding terminal, outer box grounding terminal, and outer box of the load equipment. If the same ground is used, it may not prevent electric shock.

e If the method of grounding is not correct, the electrical leakage protection device may not work efficiently, and this may lead to death from electric shock. oS display So O “va Reset The electrical leakage relay is installed to detect electrical leakage caused by defective insulation of the load used during operation EI ect akea : Se X oo ©. T~ Test but ton 50cm and to shut off the circuit. (19. 7in) PRECAUTIONS FOR USE e Generator ground o Carry out grounding with the supply (optional) ground bar from ground terminal @ of the output terminal board. Carry out grounding so that the grounding resistance is max. 500 Q when the electrical leakage relay detection current is 30 mA.

o Ground the outer box of the generator also from outer box ground terminal @®. AD726258 e Grounding o Carry out grounding work for the outer box of the load equipment in the same way as for the generator. load equipment CHECKING ACTUATION Check the actuation of the electrical leakage relay periodically as follows. 1. Start the generator and adjust to the rated voltage. 2. Turn the breaker ON. 3. Press the test button on the front face of the electrical leakage relay. REMARK When this is done, the electrical leakage display lamp (red) on the front face of the electrical leakage relay should light up and the breaker should break the circuit. 4.

Press the reset button, switch the breaker OFF, then switch it ON to actuate the breaker again. REMARK Once the electrical leakage relay is actuated, it will remain actuated until the reset button is pressed or the generator is stopped. 2-41