Doosan DBC 130 / F30i Series — 1.7 2008 PSM Contact Check Error

DBC 130(F30i Series) DBC130ALE2A 1.7 2008 PSM Contact Check Error 1) Description There occurred an error while KM10 magnetic contactor was operating. 2) Cause of problem The operation of KM10 did not comply with the intended signal. 3) Action ① The check signal (X9.6) of the magnetic contactor should turn on only while KM10 is operating. ② Set "Keep Relay K17.0" to 1 if you want to enable the option of Motor Power On/Off. If you set "K17.0=(1)" to enable the option of Motor Power ON/OFF, KM10 magnetic contactor turns off if the door is open, and turns on if the door is close.

19 Device Connector Signal Address I/O Numberin Symbol (Pin) Power Supply Contact On State X9.6 PMON.M -KM10 Input Module Slot 07 XJ413 (01) PMON Splash Guard Door Interlock X6.2 SDIC.M -S61 Input Module Slot 07 XJ413(48) SS61B KM10 (Magn K Auxi et) M10 (Magnet) liary “a” contact