omron — Setting Temperature Alarms

Simplicity on the Worksite Solutions Guide for FAQs: E5CC/E5EC Setting Temperature Alarms You set this parameter in the Initial Setting Level. The parameter is set to 2 (Upper-limit Alarm) by default. Turn ON the power supply. 1 Operating Display Press the Key for at least 3 seconds. 2 ← Flashes 3 times. Press the (Level ) Key for at least 3 seconds. Initial Setting Level ← in-t (IN-T) will be displayed to show that the Initial Setting Level has been entered. Change the parameter with the Key . 3 Initial Setting Level ← alt1 (ALT1): Indicates the Alarm 1 parameter. ← Default setting is 2 (Upper-limit Alarm).

Setting Temperature Alarms Press the (M ode) Key several times to display alt1 (ALT1). Set the parameter with the Keys. 4 Initial Setting Level Change the set value with and Down) Keys. Set the alarm type number that you selected on page 4-3. If required, use the (Mode) Key and the (Up and Down) Keys to repeat steps 3 and 4 and set alarm type numbers for alt2 (ALT2) (Alarm 2), alt3 (ALT3) (Alarm 3), and alt4 (ALT4) (Alarm 4).(The number of alarms that is supported depends on the model of Temperature Controller.

Some of the alarm parameters may not be displayed.) (When finished, press the (Level) Key for at least 1 second to return to the operation display.) * If the Controller is equipped with HB and HS alarm detection, the Alarm 1 Type is not displayed for the default settings. To use alarm 1, set the output assignment to alarm 1. 4-6 Simplicity on the Worksite Solutions Guide for FAQs: E5CC/E5EC S tep 2 Setting Alarm Parameters 1 Setting the Alarm Type (U