Simplicity on the Worksite Solutions Guide for FAQs: E5CC/E5EC Setting Temperature Alarms You set the alarm value in the Operation Level. The following procedure continues on from the procedure to set the Alarm Type parameter (Initial Setting Level). Start here if you j ust turned ON the power supply. Press the Key for at least 1 second. 1 Initial Setting Level Press the (Level) Key for at least 1 second. Operation Level Change the parameter with the Ke y.
2 Setting Alarm Type 2, 3, 6, 7, 8, 9,10, or 11 (Upper-limit Alarms and Lower-limit Alarms) Setting Alarm Type 1, 4, or 5 (Upper-limit and Lower-limit Alarms or Upper-limit and Lower-limit Range Alarms) Press the (Mode) Key Press the (Mode) Key several times to display al1h (AL1H). Setting Temperature Alarms several times to display al-1 (AL-1). Simplicity on the Worksite Solutions Guide for FAQs: E5CC/E5EC 4-7 2 Setting the Alarm Value