omron — Setting Temperature Alarms

Simplicity on the Worksite Solutions Guide for FAQs: E5CC/E5EC Setting Temperature Alarms You set this parameter in the Initial Setting Level. The parameter is set to 0.2°C by default. Turn ON the power supply. 1 Operating Display 2 Press the K ey for at least 3 seconds. Press the (Level) Key for at least 3 seconds. Initial Setting Level ← in-t (IN-T) will be displayed to show that the Initial Setting Level has been entered. Change the parameter with the Key. 3 Initial Setting Level alh1 (ALH1): ← Indicates the Alarm 1 Hysteresis parameter. Press the (Mode) Key several times to display alh1 (ALH1). ← Default setting is 0.2°C. Setting Temperature Alarms Set the parameter with the Keys.

4 Initial Setting Level Change the set value with the (Up and Down) Keys If required, use the (Mode) Key and the (Up and Down) Keys to repeat steps 3 and 4 and set the hysteresis for alh2 (ALH2) (Alarm 2 Hysteresis), alh3 (ALH3) (Alarm 3 Hysteresis), and alh4 (ALH4) (Alarm 4 Hysteresis) (The number of alarms that is supported depends on the model of Temperature Controller. Some of the alarm parameters may not be displayed.) (When finished, press the (Level) Key for at least 1 second to return to the operation display.) 4-10 Simplicity on the Worksite Solutions Guide for FAQs: E5CC/E5EC 2 Setting the Hysteresis