omron — Setting Temperature Alarms

Simplicity on the Worksite Solutions Guide for FAQs: E5CC/E5EC Setting Temperature Alarms Reversing Outputs You can reverse the status of an auxiliary output (alarm output) before it is actually output. With the default setting, the output will be ON when the alarm is ON and OFF when the alarm is OFF (NO: Close in Alarm). You can change the setting so that the output will be ON when the alarm is OFF and OFF when the alarm is ON (NC: Open in Alarm). Go to the Advanced Function Setting Level. 1 * For details, refer to the E5CC/E5EC Digital Temperature Controllers User's Manual (Cat. No. H174).

Refer to Moving to the Advanced Function Setting Level page 4-14 for the procedure to enter the Advanced Function Setting Level. Advanced Function Setting Level ← init (INIT) will be displayed to show that the Advanced Function Setting Level has been entered. 2 Advanced Function Setting Level sb1n (SB1N): Indicates the Auxiliary ← Output 1 Open in Alarm parameter. ← Default setting is n-o (N-O): Close in Alarm Press the (Mode) Key several times to display sb1n (SB1N). Set the parameter with the Keys. 3 Advanced Function Setting Level Change between Open in Alarm and Close in Alarm with the (Up and Down) Keys. Setting Temperature Alarms n-o (N-O): Close in Alarm n-c (N-C):

Open in Alarm If required, use the (Mode) Key and the (Up and Down) Keys to repeat steps 2 and 3 and set Open in Alarm or Close in Alarm for sb2n (SB2N) (Auxiliary Output 2 Open in Alarm), sb3n (SB3N) (Auxiliary Output 3 Open in Alarm), and sb4n (SB4N) (Auxiliary Output 4 Open in Alarm). (The number of auxiliary outputs that is supported depends on the model of Temperature Controller. Some of the auxiliary output parameters may not be displayed.) (When finished, press the (Level) Key for at least 1 second to return to the Initial Setting Level.) Simplicity on the Worksite Solutions Guide for FAQs: E5CC/E5EC 4-11 Reference Information:

Other Related Settings Change the parameter with the Ke y.