Delta DVP-ES3 — 2.1 General Specifications

Chapter 2 Specifications and System Configuratio n 2.1 General Specifications 2_ 2-2 Item Specifications Operating temperature -0 to 55°C Storage temperature -40 to 70°C 5–95% No condensation Operating humidity 5–95% No condensation Storage humidity Work environment No corrosive gas exists. Installation location In a control box Pollution degree 2 Ingress protection IP20 (IP ratings) EMC (electromagnetic Refer to Appendis C for more information. compatibility) Tested with: 5 Hz ≦ f ≦ 8.4 Hz, constant amplitude 3.5 mm; 8.4 Hz ≦ f ≦ 150 Hz, constant acceleration 1g Duration of oscillation:

10 sweep cycles per axis on each direction of the three mutually perpendicular axes International Standard IEC 61131-2 & IEC 60068-2-6 (TEST Fc) Vibration resistance Tested with: Half-sine wave: Strength of shock 15 g peak value, 11 ms duration; Shock direction: The shocks in each in direction per axis, on three mutually perpendicular axes (total of 18 shocks) International Standard IEC 61131-2 & IEC 60068-2-27 (TEST Ea) Shock resistance Safety Conforms to IEC 61131-2, UL 61010-2-201 Ambient air Operating: 1080 ~ 795hPa (-1000 ~ 2000 m) Storage:1080 ~ 660hPa (-1000 ~ 3500 m) temperature-barometric pressure-altitude