2 Functions of Devices in DVP-PLC 3. The functions: a) Definition of the 2 axes: X axis: Y0 (direction output) and Y10 (pulse output) Y axis: Y1 (direction output) and Y11 (pulse output) b) Define the format of output table: Assume D1133 = K100 and D1134 = K3 and the output table has to be set as: Note: The frequency and number of output pulses are all in 32-bit. Thus, the 3 sections will continuously occupy 12 D devices (3 Ч 2 Ч 2 = 12). 4. Note: a) Make sure that the output frequency and the number of pulses have been set before using this function. The output frequency and the number of pulses cannot be modified during the execution of the function.
b) When PLC program scans to END instruction, it will auto-check whether this function needs to be enabled. c) When M1133 and M1135 are set in the same scan period, the two axes will output pulses synchronously. d) When the output frequency 100kHz, the output will be executed by 100kHz. e) Only device D (D0 ~ D999 and D2000 ~ D4999) can be used for this function. DO NOT use other devices or exceed the range of device D. f) The maximum number of segments for this function is 50. When the number of segments 50, this function will be disabled. g) After this function is enabled, M1102 = “On” indicates Y10 output is completed and M1103 = “On” indicates Y11 output is completed.
DVP-PLC Application Manual 2-95 Section Output Number of Device D Device D Description No. frequency Output pulses 1 D101,D100 K10,000 D103,D102 K1,000 Section 1 outputs 1,000 pulses in 10kHz 2 D105,D104 K15,000 D107,D106 K2,000 Section 2 outputs 2,000 pulses in 15kHz 3 D109,D108 K5,000 D111,D110 K3,000 Section 3 outputs 3,000 pulses in 5kHz