DVP02TK-S/DVP02TU-S Temperature Control Module Manual _1 Analog sampling time (by channel) Response time = setting time + conversion time *1. Compared to the response time of the thermocouple temperature, it needs two times of time for the thermistor temperature to respond, since the thermistor channels require a temperature compensation. *2. Since there is only one channel used, the time to stabilize the circuit is not required.
1-4 Input impedance 650KΩ Analog / Digital Current Input Maximum rated input 0mA~20mA 4mA~20mA Overall accuracy ±0.5% (normal temperature) Overall accuracy ±1% (full temperature range) Hardware resolution 16 bits Input impedance 249Ω Analog / Digital Temperature Input Maximum rated input Thermocouple Thermistor Overall accuracy ±0.4% (normal temperature) Overall accuracy ±0.8% (full temperature range) Hardware resolution 24 bits Input impedance 2MΩ Analog input type AI Thermocouple Thermistor Quick AI (0~10V)*2 Setting time (ms) 80 80 160 3 Conversion time (ms) 50 50 100 2 Response time (ms) 130 130 260 5