Chapter 1 Introduction 1.1 Specification 1_ A/D Function Specification 1-3 DVP02TK-S/DVP02TU-S Supply voltage 24VDC Max. rated power 2.4W, supplied by external power source in compliance with UL61010-2-201 \ IEC61131-2 consumption Connector Type European standard removable terminal block (Pin pitch: 3.5mm) Operation: 0°C ~ 55°C (temperature), 5 ~ 95% (humidity), Pollution degree: 2 Storage: -25°C ~ 70°C (temperature), 5 ~ 95% (humidity), Attitude: up to 2000m; For use in dry location only Operation/storage temperature Vibration/Shock International standards:
IEC 61131-2, IEC 68-2-6 (TEST Fc) / IEC 61131-2 & IEC 68-2-27 (TEST Ea) resistance Connection to The modules are numbered from 0 to 7 automatically by their distance from DVP-PLC. Max. 8 modules are allowed to connect to DVP-PLC and will not occupy any digital I/O points. DVP-PLC 2 points of universals analog inputs (CH1, CH2), 2 analog outputs (OUT1, OUT2) or 4 digital outputs (OUT1~OUT4) I/O points General Analog Input Thermal resistance: Pt100, JPt100, Pt1000, Ni100, Ni1000, Cu50, Cu100, GNi1000 Thermocouple : J, K, R, S, T, E, N, B, U, L, TXK (L), C, PL II Voltage input: 0~+50mV, 0~+5V, 0~+10V Current input:
0mA~+20mA, 4~+20 mA CH1, Input CH2 Hardware Resolution 16 bits Distance 100 meters Input disconnection Supported by exceeded temperature input range detection Analog / Digital Output OUT1~ Analog output, 12-bit: 0~+10V, 0/4~+20mA Analog OUT2 OUT1~ 4 channels digital output, 250VAC, 60Hz/24VDC, 2A, Relay 4 channels digital output, Voltage pulse output, 24VDC, 300mA Digital OUT4 Analog / Digital Voltage Input Maximum rated input 0V~10V 0V~5V Overall accuracy ±0.5% (normal temperature) Overall accuracy ±1% (full temperature range) Hardware resolution 16 bits