E774GB — 6.4 Protective Earth Conductor

KUHNKE Automation 6.4 Protective Earth Conductor The thermo-controller is designed for installation in a switching cabinet whose IP 20 housing provides sufficient protection against direct contact. Attach a protective earth conductor to provide for protection against indirect contact in case of a fault to frame. Connection is made to the 4 mm bolt on the top or on the bottom of the device. Be sure to use a matching eyelet connector with an inside diameter of 4.3 mm to DIN 46234. Ground connection top side Ground connection bottom side The cross-section of the PE conductor not to be less than:

The connections are marked with the following symbol • 2.5mmІ Cu or 16mmІ Al if protection against mechanical damage is included, • 4mmІ Cu or 16mmІ Al if protection against mechanical damage is NOT included. Try to keep the lead to the earthing terminal as short as possible. Installation to conform to the protective earth connection regulations of EN 50178! 28 E 774 GB 30.06.2014