sinee — EM303B User Manual (EN)

User Manual EM303B General Purpose Inverter Set F0-03=0 and F0-26=2, i.e. the inverter can be set as speed process PID control mode. The control object is the speed of motor. Setting Channel Options F4-00=0 Numeric PID setting. Input PID setting value by editing F4-01 parameters through keypad. F4-00=1 Take input voltage of analog input terminal VS as PID setting value. F4-00=2 Convert the input current of analog input terminal IS into the voltage, and then take the voltage as PID setting value. F4-00=3 Take input voltage of analog input terminal VF as PID setting value.

F4-00=4 Convert the input current of analog input terminal IF into the voltage, and then take the voltage as PID setting value. F4-00=5 Take VP input voltage set by keypad potentiometer as PID setting value. PID Numeric Setting The data of F4-01 can be directly input by keypad as PID setting value. PID feedback signal is input by the analog input terminal. The feedback value can be operated mathematically based on real needs. F4-02=0 VF input voltage is PID feedback. F4-02=1 IF input current is PID feedback. F4-02=2 VS input voltage is PID feedback. F4-02=3 IS input current is PID feedback. 112 No. Function Range Unit Default Type PID Regular Setting Mode 0: Numeric PID Setting 1: VS 2:

IS 3: VF 4: IF 5: VP 0 〇 F4-00 F4-01 PID Numeric Setting 0.0~PID Maximum Scale V 0.0 ● No. Function Range Unit Default Type PID Feedback Options 0: VF 1: IF 2: VS 3: IS 0 〇 F4-02 No. Function Range Unit Default Type F4-03 PID Maximum Scale 0.1~6000.0 10.0 ●