sinee — EM303B User Manual (EN)

User Manual EM303B General Purpose Inverter F5-11 FA-06 sets analog signals ( VS/VF/IS/IF/VP ) *torque setting value. Figure 1-2 Torque Setting Mode 1.2.4 Start/Stop Control Mode of Inverter The start/stop control mode of inverter refers to the modes to start/stop control of inverter. There are 3 control modes: keypad control mode, terminal control mode, and RS485 communication control mode. Terminal control mode is categorized as 2-wire sequence, and 3-wire sequence. See Figure 1-3 for the control logic of terminal control mode. F5-12 is the setting value of primary numeric torque. K1 PLC 24V K1 PLC 24V RUN Xi RUN Xi K2 COM F/R K2 COM F/R 0:

On 1:Off 0:On 1:Off (a) 2-wire sequence 0 (F0-05=0) (b) 2-wire sequence 1 (F0-05=1) PLC 24V PLC 24V RUN RUN F/R Xi F/R Xi 0: On 1: Off ( c ) 3-wire sequence 0 (F0-05=2) (d) 3-wire sequence 1(F0-05=3) COM COM Figure 1-3 Control Logic of Terminal Control Mode 12 0: Primary Numeric Torque Setting 1: VP Keypad Potentiometer 2:VS 3:IS 4:VF 5:IF 6:Not used 7: K1*VP+K2*(K3*VS+K4*IS+ K5*VF+K6*IF-K8*5V) Analog signal voltage/10*100% Analog signal current/20*100% FA-06:

the ones place 0:Present Setting Value 1:VS*Present Setting Value 2:VF*Present Setting Value 3:IS*Present Setting Value Torque Setting 4:IF*Present Setting Value K1 K2 Run Command 0 0 Reverse 0 1 Forward 1 0 Stop 1 1 Stop K1 K2 Run Command 0 0 Stop 0 1 Forward 1 0 Reverse 1 1 Stop RUN Run Button Xi Stop Button F/R 1 Forward 0 Reverse RUN Forward Button F/R Reverse Button Xi Stop Button