sinee — EM303B User Manual (EN)

User Manual EM303B General Purpose Inverter 8.11.5 Auxiliary Speed Setting Mode F9-05=0 Defined by the value of F9-06. F9-05=1 Set by VP keypad potentiometer. F9-05=2 Set by the voltage of analog terminal VS. F9-05=3 Set by the current of analog terminal IS. F9-05=5 Set by K3*VS+K4*IS (Input signals VS and IS) F9-05=6 Setting frequency is set by K3*VS+K5*VF (Input voltage signals VS and VF) F9-05=7 Setting frequency is set by:

K4*IS+K6*IF (Input current signals IS and IF) F9-05=8 Setting frequency is set by the greater value between K3*VS and K5*VF (Inputs of 2 terminals) F9-05=9 Setting frequency is set by the greater value between K4*IS and K6*IF (Inputs of 2 terminals) F9-05=10 Setting frequency is set by: K1*VP+K2*(K3*VS+K4*IS+K5*VF+K6*IF-K8*5V) (All input signals) 8.11.6 Multi-function Output Related to Frequency Detection If multi-function output or relay output=20 (Frequency of zero speed detection), and when inverter is running, if the output frequency as inverter runs at zero speed, and the corresponding output terminal will be on.

F9-10 is to delay the action of output terminal corresponding to zero speed detection when zero speed detection is enabled. 141 No. Function Range Unit Default Type Auxiliary Speed Setting Mode 0: Auxiliary numeric frequency 1: VP 2: VS 3: IS 4: Not Used 5: K3*VS+K4*IS 6: K3*VS+K5*VF 7: K4*IS+K6*IF 8: MAX{K3*VS,K5*VF} 9: MAX{K4*IS,K6*IF} 10:K1*VP+K2*(K3*VS+K4*IS +K5*VF+K6*IF-K8*5V) 0 〇 F9-05 Auxiliary Numeric Frequency Setting 0.00~Fmax/0.0~Fmax Hz 0.00 ● F9-06 No. Function Range Unit Default Type Frequency of Zero Speed Detection 0.00~50.00/0.0~50.0 Hz 0.00 〇 F9-09 No. Function Range Unit Default Type F9-10 Zero Speed Detection Output Delay 0.00~600.00 S 1.00 〇