User Manual EM303B General Purpose Inverter deceleration, t1 = the setting value of FC-01* Deceleration time, t2= the setting value of FC-02* Deceleration time. Frequency Linear Mode S Curve Mode Deceleration Time Figure 7-23 Acceleration/Deceleration Control Acceleration Time 8.13.2 Fan Control FC-03 selects the conditions for fan to run. FC-03=0 Fan runs at power-on. FC-03=1 Fan runs while inverter is running. FC-04 selects the delay time for fan turned-on. In default status, the fan will stop after the inverter is stopped for 30 seconds. 8.13.3 Reset Previous Working Status FC-06=0 Inverter will not reset previous working status.

FC-06=1 Inverter remains the previous work status before power failure after it was powered-on. 8.13.4 Current Control and Energy Saving 147 t t1 t2 t2 t1 t t1 t2 t2 t1 No. Function Range Unit Default Type Fan Control 0: Run at power-on 1: Run at start-up 1 〇 FC-03 FC-04 Fan Delay Time 0.00~600.00 S 30.00 ● No. Function Range Unit Default Type Reset previous working status at power-on 0: Not Reset 1: Reset 0 〇 FC-06 No. Function Range Unit Default Type Current Stall Control 0: Disabled 1: Not Used 2: Enabled 2 〇 FC-07 FC-08 Overcurrent Stall Current 50.00~180.00 % 150.00 〇 Current Limit Coefficient of Weak Flux 0.20~1.00 0.70 〇 FC-09