sinee — EM303B User Manual (EN)

User Manual EM303B General Purpose Inverter 8.13.8 Energy Saving Operation FC-10=1, energy saving operation control is enabled. When inverter runs in idling or on light load (output current of inverter energy saving starting frequency (Set by FC-11), inverter will test load current automatically and make a record of time. If the setting time of FC-13 can meet energy saving needs, the output voltage shall be dropped to energy saving permitted range (Set by FC-14) to start energy saving operation. When output frequency increasing, inverter will withdraw from energy saving operation status. Output voltage will reset corresponding value.

If output current of inverter > the setting value of FC-12, automatic energy saving is disabled. See Figure 7-34 for operation process of automatic energy saving. Output Frequency ( Hz ) Output Voltage(%) Energy Saving Permitted Range FC-14 See Figure 7-34 Operation Process of Automatic Energy Saving In V/F control mode, the percentage of output voltage is the energy saving permitted range. 149 No. Function Range Unit Default Type Energy Saving Operation Options 0: Energy saving operation disabled 1:

Energy saving operation enabled 0 〇 FC-10 Energy Saving Running Initial Frequency 10.00~600.00/10.0~600.0 Hz 20.00 〇 FC-11 Energy Current Detecting Range 20.00~80.00 % 40.00 〇 FC-12 Energy Saving Delay Start Time 0.01~60.00 S 0.50 〇 FC-13 Permitted Energy Saving Range 60.00~100.00 % 80.00 〇 FC-14 Starting Frequency of Energy Saving Operation FC-11 Energy Saving Delay Start Time FC-13 Tim Energy Saving Delay Start Time FC-13 Energy Saving Operation