User Manual EM303B General Purpose Inverter 7.1.1 E0 Group: Fault Parameters 64 7 523 C0-11 C0-12 Output Current Percentage 0.00~300.00 % × 524 C0-13 Effective Output Current Value 0.0~3000.0 A × 525 No.
Function Range Unit Default Type S/N C0-14 Output Voltage Percentage 0.00~200.00 % × 526 C0-15 Effective Output Voltage Value 0.0~660.0 V × 527 C0-16 DC Bus Voltage 0~1200 V × 528 C0-17 Output torque percentage 0.00~200.00 % × 529 C0-18 Not Used × 530 C0-19 Program Operation Section 1~7 × 531 Running Time of Present Sectio of ProgramOperation n 0.0~6000.0 S/min × 532 C0-20 C0-21 Output Power 0.0~3000.0 kW × 533 C0-22 PID Input 0.0~PID Maximum Scale × 534 C0-23 PID Calculation Feedback 0.00~PID Maximum Scale × 535 C0-24 Torque CurrentInput Iq* 0.00~200.00 % × 536 C0-25 Torque CurrentFeedback Iq 0.00~200.00 % × 537 Input Terminal Status X7 X6 X5 X4 X3 X2 X1 × 538 C0-26 0 0 0 0 0 0 0 Output Terminal Status * * * * R1 Y2 Y1 × 539 C0-27 0 0 0 0 0 0 0 C0-28 VS Input Monitoring 0-10000 × 540 C0-29 IS Input Monitoring 0-10000 × 541 C0-30 VF Input Monitoring 0-10000 × 542 C0-31 IF Input Monitoring 0-10000 × 543 No.
Function Range Unit Default Type S/N Fault Trips 00: No fault SC:Drive Fault/OutputShortcircuit/EMC fault HOC: Instantaneous overcurrent HOU: Instantaneous overvoltage SOC: Stable overcurrent SOU: Stable overvoltage SlU: Stable undervoltage/SOFT Soft-start failure IlP: Input phase loss Ol: Inverter Overload OL1: Motor Overload(OL &OL1 displayed as OL on the keypad) OH: Overheat 0 × 544 E0-00