sinee — 6.2 Function Parameter Table

EM500 Open-Loop Vector Control Inverter User Manual 100 F07.15 Numeric Output Action at Fault Retry 0: Disabled 1: Enabled 0 〇 F07.16 Fault Retry Interval 0.01 - 30.00 s 0.50 ● F07.17 Recovery Time of Fault Retry Times 0.01 - 30.00 s 10.00 ● F07.18 Fault Retry Ilp HOU HOC SlU SOU SOC **0 00000 〇 0: Permitted 1: Not Permitted F07.19 Action 1 at Fault E21 E16 E15 E14 E13 E12 Olp Il p 000 00000 〇 0: Coast to Stop 1: Stop as per Set Stop Mode F07.20 Action 2 at Fault E28 E27 E25 E23 *0000 〇 0: Coast to Stop 1: Stop as per Set Stop Mode F07.21 Offload Protection 0: Disabled 1:

Enabled 0 ● F07.22 Offload Detection Level 0.0 - 100.0 % 20.0 ● F07.23 Load Detection Time 0.0 - 60.0 s 1.0 ● F07.24 Offload Protection 0: Coast to Stop 1: Stop as per Set Stop Mode 1 〇 F07.25 - F07.26 Not Used F07.27 AVR 0: Disable 1: Enable 2:

Automatic 1 〇 F07.28 Stall fault detection time 0.0~6000.0 s 300.0 〇 F07.29 The intensity of stall control 0~100 % 100 〇 F08 Preset Speed and Simple PLC F08.00 Preset Speed 1 0.00 - Maximum Frequency F00.16 Hz 0.00 ● F08.01 Preset Speed 2 0.00 - Maximum Frequency F00.16 Hz 5.00 ● F08.02 Preset Speed 3 0.00 - Maximum Frequency F00.16 Hz 10.00 ● F08.03 Preset Speed 4 0.00 - Maximum Frequency F00.16 Hz 15.00 ● F08.04 Preset Speed 5 0.00 - Maximum Frequency F00.16 Hz 20.00 ●