EM500 Open-Loop Vector Control Inverter User Manual 99 0: Valid Protection 1: Protection blocked 00000 F07.01 Motor Overload Protection Gain 0.20 - 10.00` 1.00 ● F07.02 Motor Overload Pre-Alarming Factor 50 - 100 % 80 ● F07.03 Motor Temperature Sensor Type 0: No Temperature Sensor 1: PT100 2: PT1000 3: KTY84-130/150 4: PTC130/150 0 ● F07.04 Motor Overheating Protection Threshold 0 - 200 ℃ 110 ● F07.05 Motor Overheating Pre-Alarming Threshold 0 - 200 ℃ 90 ● F07.06 Bus Voltage Control Options 0: Disabled 1: Undervoltage Stall, Enabled 2: Overvoltage Stall, Enabled 3:
Overvoltage Stall and Undervoltage Stall, Enabled 2 〇 F07.07 Overvoltage Stall Control Voltage 110.0 - 150.0 (380V,100.0=537V) % 131.0 (703V) 〇 F07.08 Undervoltage Stall Control Voltage 60.0 - Judgment Voltage at Power Failure Ending (100.0= Standard Bus Voltage) % 76.0 〇 F07.09 Judgment Voltage at Power Failure Ending Undervoltage Stall Control Voltage - 100.0 % 86.0 ● F07.10 Judgment Delay Time at Power Failure Ending 0.00 - 100.00 s 5.00 ● F07.11 Current Limit Control 0: Disabled 1: Limit Mode 1 2: Limit Mode 2 2 〇 F07.12 Current Limit Level 20.0 - 180.0 (100.0= Inverter Rated Current) % 150.0 ● F07.13 Rapid Current Limit 0: Disabled 1: Enabled 0 〇 F07.14 Fault Retry Times 0 – 20, 0:
Fault Retry Disabled 0 〇