EM500 Open-Loop Vector Control Inverter User Manual 128 F15.29 ADT2 Hysteresis 0.00 - F15.28 (Monotonic Downward is active) % 5.00 ● F15.30 Energy Consumption Brake 0: Disabled 1: Enabled 0 〇 F15.31 Energy Consumption Brake Operation Voltage 110.0 - 140.0 (380V, 100.0=537V) % 125.0 (671V) ● F15.32 Brake Duty Ratio 20 - 100 (100 means that duty ratio is 1) % 100 ● F15.33 Control Mode of Set Frequency Lower Than Lower Limit Frequency 0: Run at Lower Limit Frequency 1: Stop 2: Run at Zero Speed 0 〇 F15.34 Fan Control 0: Run at Energization 1: Run at Start 2:

Run at Intelligent Temperature Control 1 〇 F15.35 Over modulation Intensity 1.00 - 1.10 1.05 ● F15.36 PWM Modulation Method Switching Options 0: Disabled (7 preset PWM modulation) 1: Enabled (5 preset PWM modulation) 0 〇 F15.37 PWM Modulation Method 0.00 - Maximum Frequency F00.16 Hz 15.00 ● F15.38 Deadband Compensation Mode 0: Disabled 1: Compensation Mode 1 2: Compensation Mode 2 1 〇 F15.39 Terminal Jog Priority 0: Disabled 1: Enabled 0 〇 F15.40 Deceleration Time at Rapid Stop 0.00 - 650.00 (F15.13=0) 0.0 - 6500.0 (F15.13=1) 0 - 65000 (F15.13=2) s 1.00 ● F15.41 ~ F15.43 Not Used F15.44 Phase Angle Adjustment Enabled 0: Enbabled 1:

Shut Down 0 ● F15.45 Power frequencyVariable frequency-Power frequency switching 0: Automatic 1: Manual 0 〇