EM500 Open-Loop Vector Control Inverter User Manual X7. F00.04 has the same meanings as AI1-AI4 and X7. 100.00% is the percentage inputted through Synthetic Frequency of Main and Auxiliary Channels. Acceleration time refers to the time required for output frequency going from 0.00Hz to the acceleration/deceleration reference frequency Fbase, or the time required for output frequency coming down from the acceleration/deceleration reference frequency Fbase to 0.00Hz; this has nothing to do with forward/reverse.See Figure 7-4.
Output Frequency (Hz) Fbase Output Frequency (Hz) Fbase Fbase Fbase t1 t (s) t2 t (s) (a) Acceleration Time 1 (b) Deceleration Time 1 Figure 7–4 Acceleration/Deceleration Time Note: There are three acceleration/deceleration time units, 0.01 s, 0.1 s and 1 s, which are determined through F15.13. F00.16 is the maximum frequency allowed by inverter and denoted by Fmax (range: 1.00 - 600.00 Hz). 165 No. Function Range Unit Default Type F00.14 Acceleration Time 1 0.00 - 650.00 (F15.13=0) 0.0 - 6500.0 (F15.13=1) 0 - 65000 (F15.13=2) s 15.00 ● F00.15 Deceleration Time 1 0.00 - 650.00 (F15.13=0) 0.0 - 6500.0 (F15.13=1) 0 - 65000 (F15.13=2) s 15.00 ● No.
Function Range Unit Default Type F00.16 Maximum Frequency 1.00 - 600.00 Hz 50.00 〇