sinee — 6.2 Function Parameter Table

EM500 Open-Loop Vector Control Inverter User Manual 90 1: Monopulse F03.06 Positive/Negative Logic of Numeric Output D7 D6 D5 D4 D3 D2 D1 D0 00000 〇 * * * Y3 R2 R1 Y2 Y1 0: Positive Logic, Enabled at On/Disabled at Off 1: Negative Logic, Disabled at On/Enabled at Off F03.07 Y2 Output Type 0: Common Numeric Output 0 〇 1: High-Frequency Pulse Output F03.08 Output Status Control at JOG D7 D6 D5 D4 D3 D2 D1 D0 00000 〇 * * * REV FDT2 FDT1 FAR RUN 0: Enabled at JOG 1:

Disabled at JOG F03.09 Y1 Effective Delay Time 0.000 - 30.000 s 0.000 ● F03.10 Y1 Ineffective Delay Time 0.000 - 30.000 s 0.000 ● F03.11 Y2 Effective Delay Time 0.000 - 30.000 s 0.000 ● F03.12 Y2 Ineffective Delay Time 0.000 - 30.000 s 0.000 ● F03.13 R1 Effective Delay Time 0.000 - 30.000 s 0.000 ● F03.14 R1 Ineffective Delay Time 0.000 - 30.000 s 0.000 ● F03.15 R2 Effective Delay Time 0.000 - 30.000 s 0.000 ● F03.16 R2 Ineffective Delay Time 0.000 - 30.000 s 0.000 ● F03.17 Y1 Monopulse Output Time 0.001 - 30.000 s 0.250 ● F03.18 Y2 Monopulse Output Time 0.001 - 30.000 s 0.250 ● F03.19 R1 Monopulse Output Time 0.001 - 30.000 s 0.250 ● F03.20 R2 Monopulse Output Time 0.001 - 30.000 s 0.250 ● F03.21 Analog Output M1 0:

Running Frequency (absolute value) 1: Set Frequency (absolute value) 2: Output torque (absolute value) 0 〇 F03.22 Analog Output M2 2 〇 F03.23 Y2 High-Frequency 11 〇