sinee — 6.2 Function Parameter Table

EM500 Open-Loop Vector Control Inverter User Manual 91 Pulse Output Function 3: Set Torque (absolute value) 4: Output Current 5: Output Voltage 6: Bus voltage 7: Output power 8: AI1 9: AI2 10: AI3 11: AI4 (Expansion Card) 12: High-Frequency Pulse Input (100.00% Corresponding to Maximum Frequency, 0.00% Corresponding to Minimum Frequency) 13: Not Used 14: The Count Value 15: Length Value 16: The PID Output Percentage 18: PID Feedback 19: PID Given 20~37: Not Used 38:

The Fan Speed Output F03.24 100% Frequency of Y2 High-Frequency Pulse Output 0.00 - 100.00 kHz 50.00 ● F03.25 0% Frequency of Y2 High-Frequency Pulse Output 0.00 - 100.00 kHz 0.00 ● F03.26 Filter Time of Y2 High-Frequency Pulse Output 0.00 - 10.00 s 0.10 ● F03.27 M1 Output Offset -100.0 - 100.0 % 0.0 ● F03.28 M1 Output Gain -10.00 - 10.00 1.00 ● F03.29 M2 Output Offset -100.0 - 100.0 % 0.0 ● F03.30 M2 Output Gain -10.00 - 10.00 1.00 ● F04 Start/Stop Control Parameter Group F04.00 Start Mode 0: Start Directly 1: Rotation Speed Tracking Start 0 〇 F04.01 Start Frequency 0.00 - 10.00 Hz 0.00 〇 F04.02 Start Frequency Retention Time 0.00 - 60.00, Disabled at 0.00 s 0.00 〇