sinee — 6.2 Function Parameter Table

EM500 Open-Loop Vector Control Inverter User Manual 92 F04.03 DC Brake Current at Start 0.0 - 100.0 (100.0= Motor Rated Frequency) % 100.0 〇 F04.04 DC Brake Time at Start 0.00 - 30.00 s 0.00 〇 F04.05 Not Used F04.06 Pre-Excitation Current 50.0 - 500.0 (100.0=Idling Current) % 100.0 〇 F04.07 Pre-Excitation Time 0.00 - 10.00 s 0.10 〇 F04.08 Rotation Speed Tracking Method 0: Start from Maximum Frequency 1: Start from Stop Frequency 2:

Start from Power frequency 0 〇 F04.09 Rise Time of Rotation Speed Tracking Voltage 0.05 - 10.00 s 0.30 〇 F04.10 Deceleration Time of Rotation Speed Tracking 0.1 - 20.0 s 2.0 〇 F04.11 Rotation Speed Tracking Current 30.0 - 150.0 (100.0=Inverter Rated Current) % 60.0 ● F04.12 Rotation Speed Tracking Compensation Gain 1.00 - 1.30 1.05 ● F04.13 Not Used F04.14 Acceleration/Decele ration Mode 0: Linear Acceleration/Deceleration 1:

S Curve Acceleration/Deceleration 0 〇 F04.15 S Curve Start Section Time at Acceleration 0.00 - System acceleration time/2 (F15.13=0) 0.0 - System acceleration time/2 (F15.13=1) 0 - System acceleration time/2 (F15.13=2) s 1.00 ● F04.16 S Curve End Section Time at Acceleration 0.00 - System acceleration time/2 (F15.13=0) 0.0 - System acceleration time/2 (F15.13=1) 0 - System acceleration time/2 (F15.13=2) s 1.00 ● F04.17 S Curve Start Section Time at Deceleration 0.00 - System deceleration time/2 (F15.13=0) 0.0 - System deceleration time/2 (F15.13=1) 0 - System deceleration time/2 (F15.13=2) s 1.00 ●