User Guide of EM730 Series Inverter 5.5 Start and Stop Control F00.02=0: keyboard control The start and stop of the inverter are controlled by the RUN key, STOP key on the keyboard. In the case of no trip protection, press the RUN key to enter the running status. If the green LED indicator above the RUN key is normally ON, it indicates that the inverter is running. If this indicator is flickering, it indicates that the inverter is in the status of deceleration to stop. F00.02=1: terminal control The inverter start and stop are controlled by the start and stop control terminals defined by the function code F02.00 to F02.04. Terminal control is dependent on F00.03. F00.02=2:
communication control The inverter start and stop are controlled by the host through the RS485 communication port. F04.00=0: direct start The inverter is started at the starting frequency, following the DC braking (not suitable when F04.04=0) and pre-excitation (not suitable when F04.07=0). The starting frequency will change to the set frequency after the holding time. The inverter is smoothly started at the current rotating frequency of the motor, following the speed tracking. F04.00=1: start with speed tracking F04.19=0: deceleration to stop The motor decelerates to stop according to the set deceleration time [default setting: based on F00.15 (deceleration time 1)]. F04.19=1:
free stop When there is a valid stop command, the inverter will stop output immediately, and the motor will freely coast to stop. The stop time depends on the inertia of the motor and load. 40 Functio Function code Default Parameter description Attribute n code name setting F00.02 Options of command source 0: keyboard control 1: Terminal control 2: Communication control 0 〇 Function Function code Default Parameter description Attribute code name setting F04.00 Start-up method 0: direct start 1: start of speed tracking 0 〇 Function Function code Default Parameter description Attribute code name setting F04.19 Stop mode 0: Slow down to stop 1: Free stop 0 〇