User Guide of EM730 Series Inverter 5.5.1 Terminal control of start and stop Terminal RUN: Xi terminal is set to “1: terminal RUN” Terminal F/R: Xi terminal is set to “2: running direction F/R” Terminal control can be divided into two types: two-line control and three-line control. Two-line control: F00.03=0: the terminal RUN is enabled and the terminal F/R controls forward/reverse running. Enable/Disable the terminal RUN to control the start and stop of the inverter, and the terminal F/R to control the forward/reverse running. If F00.21 is set to 1 and reverse running is disabled, the F/R terminal will not be available.

When the mode of deceleration to stop is selected, the logic diagram is as shown in Fig. 5-2 (b). F00.03=1: the terminal RUN controls forward running, and the terminal F/R is in the reverse mode. Enable/Disable the terminal RUN to control the forward running and stop of the inverter, and the terminal F/R to control the reverse running and stop. When the terminals RUN and F/R are enabled simultaneously, the inverter will be stopped. If reverse running is disabled, the terminal F/R will not be available. When the mode of deceleration to stop is selected, the logic of forward/reverse running is as shown in Fig.

5-2 (d) ; (a) Wiring diagram of two-line control (F00.03=0) (b) F04.19=0, F00.03=0, run the forward/reverse logic. 41 Functio Function code Default Parameter description Attribute n code name setting F00.03 Options of terminal control mode 0: terminal RUN (running) and F/R (forward/reverse) 1: terminal RUN (forward) and F/R (reverse) 2: terminal RUN (forward), Xi (stop) and F/R (reverse) 3: terminal RUN (running), Xi (stop) and F/R (forward/reverse) 0 〇