User Manual of EM730/EM730E Series Inverter Enable/Disable the terminal RUN to control the start and stop of the inverter, and the terminal F/R to control the forward/reverse running. If F00.21 is set to 1 and reverse running is disabled, the F/R terminal will not be available. If the mode of deceleration to stop is selected, the logic diagram is as shown in Fig. 7-6(b); F00.03=1: the terminal RUN controls forward running, and the terminal F/R is in the reverse mode. Enable/Disable the terminal RUN to control the forward running and stop of the inverter, and the terminal F/R to control the reverse running and stop.

When the terminals RUN and F/R are enabled simultaneously, the inverter will be stopped. If reverse running is disabled, the terminal F/R will not be available. If the mode of deceleration to stop is selected, the forward/reverse logic will be run, as shown in Fig. 7-6(d); 24V Inverter RUN Operation F/R Forward/reverse COM (a) Wiring diagram of two-line control (F00.03=0) (b) F04.19=0, F00.03=0, run the forward/reverse logic 24V Forward RUN (c) Wiring Inverter RUN F/R diagram F/R Reverse of two-line f COM Output frequency -f Time control (F00.03=1) (d) F04.19=0, F00.03=1: forward/reverse running logic Fig.

7-6 Two-line Control When the start/stop value of F00.03 is set to 0 or 1, even if the terminal RUN is available, the inverter can be stopped by pressing the STOP key external stop command to the terminal. In this case, the inverter will not be in the or sending an 131