User Manual of EM730/EM730E Series Inverter input lines or excessive on-site interference resulting in significant input fluctuations. In principle, this function code should be minimized. lower limits corresponding to the range. Select the input type of AI1 and AI2: current or voltage type. Determine the upper and F02.62 =0: 0~10V AI1 is the voltage type, with a range of 0-10V. The input voltage (0-10V) corresponds to the setting 0%-100%. 0V corresponds to 0%, and +10V corresponds to 100%. F02.62 =3: -10~10V AI1 is the voltage type, with a range of -10-10V. The input voltage (-10 to 10V) corresponds to the setting -100% to 100%. -10V corresponds to -100%, and +10V corresponds to 100%.
F02.62 =4: 0~5V AI1 is the voltage type, with a range of 0-5V. The input voltage (0-5V) corresponds to the setting 0%-100%. 0V corresponds to 0%, and +5V corresponds to 100%. F02.63 =0: 0~10V the setting 0%-100%. 0V corresponds to 0%, and +10V corresponds to 100%. AI2 is the voltage type, with a range of 0-10V. The input voltage (0-10V) corresponds to F02.63=1: 4-20mA (adjust the short circuit cap of the control panel to the current mode) AI2 is the current type, with a range of 4-20mA. The input current (4-20mA) corresponds to the setting 0%-100%. The current of 4mA or less corresponds to 0%, and 20mA corresponds to 100%. F02.63=2:
0-20mA (adjust the short circuit cap of the control panel to the current 165 Function Default Function code name Parameter description Unit Attribute code setting F02.62 Selection of analog input AI1 type 0: 0~10V 3: -10~10V 4: 0~5V 0 〇 F02.63 Selection of analog input AI2 type 0: 0~10V 1: 4~20mA 2: 0~20mA 4: 0~5V 0 〇