User Manual of EM730/EM730E Series Inverter four running modes in total, as detailed in Table 7-13. Table 7-13 Details of PLC Running Mode ★ The last segment refers to the segment that is not set to 0, judged from the running time (F08.48) of the 15 th segment toward the 1 st segment. Output frequency (Hz) 5 1 2 Time (s) 4 12 T1 T2 T4 T5 T12 T13 13 Fig. 7-26 Schematic Diagram of Simple PLC Operation Since the running time of the 3 rd segment is set to 0 (F08.24=0.0), the 3 rd segment will not be Fig. 7-26 shows the operation diagram in the running mode “0: stop after a single run”. put into actual operation.
The running time of the 14 th and 15 th segments is set to 0 (F08.46=0.0, F08.48=0.0), so the last segment is the 13 th segment, and the inverter will be stopped after running in the 13 th segment. 210 F08.15 Description 0 The inverter will be stopped after running in the last segment. 1 The inverter will run cyclically and be stopped after the set cycles. The number of cycles depends on the function code F08.16. 2 The inverter will run cyclically and keep the speed of the last segment after running in the last segment, until a stop command is received. The number of cycles depends on the function code F08.16. 3 The inverter will continue cyclic operation until a stop command is received.
Function code Function code Default Parameter description Unit Attribute name setting F08.17 Simple PLC memory options Ones place: Stop memory options 0: no memory (from the first segment) 00 ●