*1 Differs according to the capacity. 6%: FR-CS84-022 or lower, FR-CS82S-042 or lower 4%: FR-CS84-036 to FR-CS84-080, FR-CS82S-070, FR-CS82S-100 3%: FR-CS84-120 and FR-CS84-160 2%: FR-CS84-230 or higher *2 Differs according to the capacity. 5 s: FR-CS84-080 or lower, 10 s: FR-CS84-120 and FR-CS84-160, FR-CS82S-042 or lower 15 s: FR-CS84-230 or higher *3 The setting range or initial value for the FR-CS84-160 or lower and FR-CS82S-100 or lower. *4 The setting range or initial value for the FR-CS84-230 or higher. *5 Available only for the three-phase power input model. *6 The value for the 200 V class. *7 The value for the 400 V class.
*8 The parameter number in parentheses is the one used (displayed) on the LCD operation panel and the parameter unit. 78 5. PARAMETERS 5.1 Parameter list Pr. Pr.
group Name Setting range Minimum setting increment Initial value Refer to page Customer setting Regeneration avoidance 882 G120 Regeneration avoidance operation selection 0 to 2 1 0 199 883 G121 Regeneration avoidance operation level 300 to 800 V 0.1 V 400 VDC*6 199 780 VDC*7 885 G123 Regeneration avoidance compensation frequency limit value 0 to 10 Hz, 9999 0.01 Hz 6 Hz 199 886 G124 Regeneration avoidance voltage gain 0 to 200% 0.1% 100% 199 Calibration parameter C2 (902)*8 T200 Terminal 2 frequency setting bias frequency 0 to 400 Hz 0.01 Hz 0 Hz 134 C3 (902)*8 T201 Terminal 2 frequency setting bias 0 to 300% 0.1% 0% 134 125 (903)*8 T202 Terminal 2 frequency setting gain frequency 0 to 400 Hz 0.01 Hz 50 Hz 134 C4 (903)*8 T203 Terminal 2 frequency setting gain 0 to 300% 0.1% 100% 134 C5 (904)*8 T400 Terminal 4 frequency setting bias frequency 0 to 400 Hz 0.01 Hz 0 Hz 134 C6 (904)*8 T401 Terminal 4 frequency setting bias 0 to 300% 0.1% 20% 134 126 (905)*8 T402 Terminal 4 frequency setting gain frequency 0 to 400 Hz 0.01 Hz 50 Hz 134 C7 (905)*8 T403 Terminal 4 frequency setting gain 0 to 300% 0.1% 100% 134 PU 990 E104 PU buzzer control 0, 1 1 1 87 991 E105 PU contrast adjustment 0 to 63 1 58 88 Clear parameter PrCL Parameter clear (0), 1 1 0 203 ALLC All parameter clear (0), 1 1 0 203 Er.CL Fault history clear (0), 1 1 0 208 — Pr.CH Initial value change list — 1 0 204 — Pr.MD Group parameter setting (0), 1, 2 1 0 79