3.5 Overview of Operating Elements Setup and Operation Setup and Operation 3.6 Programming the Standard Function The device described here is a multifunctional counter, which can be program­ med for a variety of functions, i.e. pulse counter, tachometer, timer, shift counter or batch counter functions. The first step is to set the standard func­ tion (the factory setting of the device is the “pulse counter” setting). Now continue with the programming of the function codes (Chapters 5-9) or User Times (Chapter 3.10) Programming mode Change function Save, return to counter setting:

operation + or Keep pressed and switch voltage on press press simultaneously Function code Fn, Display Row 1 Function No. Display Row 2 Setting of Standard Function 0* Pulse counter 1 Tachometer 2 Timer 3 Shift Counter 4 Batch Counter 24 25 Display Mode Reset 123456 up + dn 0 E+up =Preset2 E+dn =Preset1 E+ shift =Preset0 up + shift = Prescaler E Programming Mode Standard Funct. Function parameters: Pulse counter Operat. Mode Count frequency Tachometer Decimal point Reset Behavior Timer Set/Reset-Mode Output Memory Shift counter Display-Mode Keylock Batch counter Output signals npn/pnp selection Applic. Input/Output + many other function parameters 1