omron — 6 Parameter Table

6 Parameter Table ENGLISH I67E-EN V1000 Quick Start Guide 25 Par. Name Description L3-05 Stall Prev. Selection during Run 0:Disabled - Motor stall or overload might occur. 1:Decel Time 1 - Reduce speed using C1-02. L3-06 Stall Prev. Level dur- ing Run Sets the current level at which stall prevention during run starts to operate. Auto-Tuning T1-01 Auto-Tun- ing Mode Selection 0:Rotational Auto-Tuning 2: Terminal resistance only 3: Rotational Auto-Tuning for Energy Saving T1-02 Rated Power Sets the motor rated power (kW). T1-03 Rated Voltage Sets the motor rated voltage (V). T1-04 Rated Current Sets the motor rated current (A). T1-05 Base Frequency Sets the motor base frequency (Hz).

T1-06 Motor Poles Sets the number of motor poles. T1-07 Base Speed Sets the motor base speed (RPM). T1-11 Motor Iron Loss Iron loss for determining the Energy Saving coefficient. If unknown leave it on default. Monitor Description U1-01 Frequency Reference (Hz) U1-02 Output Frequency (Hz) U1-03 Output Current (A) U1-05 Motor Speed (Hz) U1-06 Output Voltage Reference (Vac) U1-07 DC Bus Voltage (Vdc) U1-08 Output Power (kW) U1-09 Torque Reference (% of motor rated torque) Monitor Description U1-10 Input Terminal Status U1-10=0000000 1: Digital input 1 (terminal S1 enabled) 1: Digital Input 2 (terminal S2 enabled) 1: Digital Input 3 (terminal S3 enabled) 1:

Digital Input 4 (terminal S4 enabled) 1: Digital Input 5 (terminal S5 enabled) 1: Digital Input 6 (terminal S6 enabled) 1: Digital Input 7 (terminal S7 enabled) U1-10=0000000 1: Digital input 1 (terminal S1 enabled) 1: Digital Input 2 (terminal S2 enabled) 1: Digital Input 3 (terminal S3 enabled) 1: Digital Input 4 (terminal S4 enabled) 1: Digital Input 5 (terminal S5 enabled) 1: Digital Input 6 (terminal S6 enabled) 1: Digital Input 7 (terminal S7 enabled) U1-11 Output Terminal Status U1-11=000 1: Relay Output (terminal MA-MC closed MB-MC open) 1: Open Collector Output 1 (terminal P1) enabled 1: Open collector Output 2 (terminal P2) enabled U1-12 Drive Status U1-12=00000000 1: During run 1:

During zero-speed 1: During REV 1: During fault reset signal input 1: During speed agree 1: Drive ready 1: During alarm detection 1: During fault detection U1-12=00000000 1: During run 1: During zero-speed 1: During REV 1: During fault reset signal input 1: During speed agree 1: Drive ready 1: During alarm detection 1: During fault detection U1-13 Terminal A1 input level U1-14 Terminal A2 input level U1-16 Soft Starter Output (fref after accel./decel. ramps) U1-18 OPE Fault Parameter U1-24 Pulse Input frequency