Chapter 3 PLC System Configuration & Settings Steps to store Delta device parameters from your PC to the SD card on the PLC 1. Make sure the SD card is installed on the PLC. 2. Make sure that AS Series PLC CPU is at the state of STOP. 3. Click download on the tool bar and select the option Download “Backup File” to PLC . 3. Click Start button to store the Delta C2000 parameter backup file to the SD card. Remarks:  Default backup file path AS300: \SDCard\PLC CARD\AS300\DevPara AS200: \SDCard\PLC CARD\AS200\DevPara  File naming: mmmm_nn_tt_pppppppppppppppp.par mmmm: device or module code (e.g. PLC CPU is 0000.) nn: communication port number (e.g. PLC Ethernet communication port is 03.) tt:

communication protocol type (e.g. Ethernet communication is fixed to 01.) pppppppppppppppp: device information (IP + ID + 000000 in the hexadecimal format) For example: If the device IP is 192.168.1.9 and its ID is 9, the device information is C0A80109 (IP) + 09 (ID) + 000000 = C0A8010909000000 3-111