D.3 UL Standards The L1-02 parameter sets the allowed operation time before the oL1 fault occurs when the drive is running at 60 Hz and 150% of the full load amp rating (E2-01) of the motor. Adjusting the value of L1-02 can shift the set of oL1 curves up the Y-axis of the diagram below but will not change the shape of the curves. Time (min) 10 7 3 Cold Start 1 0.4 Hot Start 0.1 0 100 200 150 Motor Current (%) (E2-01=100 %) Figure D.8 Motor Overload Protection Time 220 SIEP C710606 33A OYMC AC Drive – J1000 User Manual