Delta — 3.2.1. Power and IO Wiring

3. System Installation The relevant circuit for wiring is shown as figure 3.2.5 Figure 3.2.5 The circuit plate for the transistor output in DVP10MC11T includes the diodes with the protection function of counter potential. It is sufficient for application of the inductive load at low power and little higher frequency of On/Off change. In the case of high power or high On/Off change frequency, please additionally connect the suppression circuit according to the following figure to decrease the interference and prevent over-voltage or over-heat from damaging the transistor output circuit.

Wiring of output circuit DVP10MC11T  24V direct current power Figure 3.2.6  Fuse protector for power circuit protection;  Emergent stop button;  Loading for switch, inductance and etc.  Diode or equivalent component for suppression (  is not used but  when in smaller power).  9V Zener diode, 5W (  and  are both used when in bigger power and frequent On/Off). DVP-MC operating manual 3-5