Руководство по эксплуатации NB10 - Терминал программируемый NB Series (EN)

Оригинальное название: NB10 E5CC Template Setup Guide Rev200a

Читать онлайн

Похожие инструкции

Текст документа

Cat. No. SG-NB10-E5CC Ver2.00a Programmable Terminal NB Series Setup Guide Temperature Controller E5□C Screen Template Index 1. Template and Targeted NB-Designer .............................................................................. 2 1.1. Targeted NB-Designer............................................................................................... 2 1.2. Device Configuration ................................................................................................. 2 1.2.1. Configuration for Template Validation Device ....................................................... 2 1.2.2.

Setting of the Communications at the NB in Template ......................................... 3 1.2.3. Settings of Digital Controller ................................................................................. 3 2. Method to specify the Communication Unit No. of Digital Controller .......................... 5 2.1. Method to specify the Communications unit No. of Digital Controller in Template ..... 5 3. Method to control E5□C Template screen ...................................................................... 7 3.1. E5□C Template ......................................................................................................... 7 3.1.1.

Common Template for Each Screen .................................................................... 7 3.1.2. Menu Screen ........................................................................................................ 8 3.1.3. Operation screen .................................................................................................. 9 3.1.4. Setting Screen .................................................................................................... 11 3.1.5. Status Monitor Screen ........................................................................................ 15 3.1.6.

Variable Monitor Screen ..................................................................................... 18 3.1.7. Trend graph screen ............................................................................................ 24 3.1.8. Fault History screen ........................................................................................... 28 3.1.9. Mass modifying screen (popup screen) ............................................................. 31 4. Revision History ............................................................................................................. 32

Стр. 1

1.1. Targeted NB-Designer In order to use the Template, the following NB-Designer and NB Unit are necessary. 1.2.1. Configuration for Template Validation Device This Template is validated with the devices configured as follows. NB 7 W-TW01B E5CC- □□ E5EC- □□ PC ( Installed NB-Designer, OS : Windows 7 ) NB 10 W-TW01B Modbus-RTU COM2 USB cable RS485 cable *1: For the details of wiring RS485 cable, refer to the NB Series Host Connection Manual . 2 1. Template and Targeted NB-Designer Manufacturer Name Model Version OMRON NB-Designer - Ver.1.22 or more OMRON NB Unit NB7W-TW01B NB10W-TW01B kernel:1458 or more Rootfs:1517 or more 1.2.

Device Configuration Manufacturer Name Model Version OMRON NB Unit NB7W-TW01B NB10W-TW01B Kernel: 1458 Rootfs: 1517 OMRON NB-Designer - Ver.1.22 - ※1RS485 cable - - PC (OS: Windows7) - - USB cable (Conforms to USB2.0 A-B type) - - NB power supply(24 VDC 25W) - OMRON Digital Controller (RS485 with the Communications function) E5 C-□□ _ E5DC-□□

Стр. 2

1.2.2. Setting of the Communications at the NB in Template This section provides settings for the Communications of this Template at the NB (COM2) as follows. 1.2.3. Settings of Digital Controller Specify the following items in Digital Controller. [Adjusting level] *1 Communications writing: ON (write permission) *Default is OFF (write protect) [Communications settings level ] *1 Protocol selection : Modbus *Default is CompoWay/F Baud rate : 9.6kbps *Default is 9.6 kbps Communications parity : -- *Default is an even number. *1:

For the methods for adjusting level and Communications setting level of Digital Controller, refer to the Digital Controller E5CC/E5EC User’s Manual (H174-E1) Reference Connection Manual (V108-E1) . For changing the Baud rate at the NB, refer to the Programmable T erminal NB Series Host Specify the Baud rate exactly same as that of the Digital Controller. Wiring from the NB COM2 to the E5 C C Controller with RS485 ( Wiring from the NB COM2 to the E5 D C Controller with RS485 ) 3

Стр. 3

When changing the communication setting level of E5 □ C, Refer to the following explanation. 1) Method to modify the Communications settings The following procedure allows the communications setting to be modified. For the details, refer to the Communications Manual (H175-E1) . Change to the following Communication Settings: Protocol Setting = Mod Communication Unit = 1 (or 2 thru 4 if using 4 Controllers) Baud Rate = 9.6 Data Length = 8 Stop Bits = 1 Parity = None Wait = 20 Reference To modify settings of the Communication writing, perform it with panel operation or setting tools of the Digital Controller. 4

Стр. 4