Delta Electronics MS300 — 5-2 Main Circuit Terminals

Chapter 5 Main Circuit Terminals  MS300 (High Speed Model) 5-2 Main Circuit Terminals  It needs following additional terminal when wiring. The additional terminal dimension should comply with the following figure 1.  After crimping the wire to the ring lug (must UL approved), UL and CSA approved R/C (YDPU2) heat shrink tubing rated min 600Vac insulation shall be install over the live part. Please refer to the following figure 2. Dimensions of Ring Lug Unit:

mm 5-5 Frame AWG Kit P/N A (MAX) B (MAX) C (MIN) D (MAX) d2 (MIN) E (MIN) F (MIN) W (MAX) t (MAX) B 14 RNBS2-4 12.1 3.6 6.1 5.6 4.3 13.0 4.5 7.2 1 12 RNBS5-4 C 14 RNBS2-4 17.8 5.0 6.1 7.2 4.3 13.0 5.5 8.0 1.2 12 RNBS5-4 10 RNBS5-4 8 RNBS8-4 D 12 RNBS5-4 17.8 5.0 6.1 7.2 4.3 13.0 5.5 8.0 1.2 10 RNBS5-4 8 RNBS8-4 E 8 RNBS8-5 27.1 6.1 10.5 11.5 5.3 13.0 6.5 12.2 1.7 6 RNB14-5 4 RNBS22-5 F 6 RNBS14-6 35.0 9.0 13.3 14.0 6.2 13.0 19.5 18.0 1.8 4 RNBS22-6 2 RNBS38-6