Delta Electronics MS300 — 5-2 Main Circuit Terminals Specifications

Chapter 5 Main Circuit Terminals  MS300 Frame B Figure 5-9  If you install at Ta 50 ° C above environment, use copper wires that have a voltage rating of 600 V and are temperature resistant to 90 ° C or above.  If you install at Ta 50 ° C environment, use copper wires that have a voltage rating of 600 V and are temperature resistant to 75 ° C or 90 ° C.  To be UL installation compliant, you must use copper wires when installing. The wire gauge is based on a temperature resistance of 75 ° C, in accordance with UL requirements and recommendations. Do not reduce the wire gauge when using high-temperature resistant wires.

Table 5-4 5-8 Main Circuit Terminals Grounding Terminals R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, Models DC-, DC+/+1, +2/B1, B2 Screw Size Screw Size Max. Wire Min. Wire Max. Wire Min.

Wire & Torque & Torque Gauge Gauge Gauge Gauge (±10%) (±10%) VFD1A6MS21AFSAA 4 mm2 [12 AWG] 1.5 mm2 [16 AWG] M4 15 kg-cm [13.0 lb-in.] [1.47 Nm] 2.5 mm2 [14 AWG] 2.5 mm2 [14 AWG] M4 15 kg-cm [13.0 lb-in.] [1.47 Nm] VFD2A8MS21AFSAA 2.5 mm2 [14 AWG] VFD4A8MS21AFSAA VFD4A8MS21ANSAA VFD4A8MS21ENSAA 4 mm2 [12 AWG] 4 mm2 [12 AWG] 4 mm2 [12 AWG] VFD7A5MS23ANSAA VFD7A5MS23ENSAA VFD1A5MS43AFSAA 0.75 mm2 [18 AWG] 2.5 mm2 [14 AWG] 2.5 mm2 [14 AWG] VFD2A7MS43AFSAA VFD4A2MS43ANSAA VFD4A2MS43ENSAA VFD4A2MS43AFSAA 2.5 mm2 [14 AWG] VFD3A0MS53ANSAA 0.75 mm2 [18 AWG] 2.5 mm2 [14 AWG] 2.5 mm2 [14 AWG]