MultiPlus 2kVA 230V Store the settings by toggling DIP switch 3 one time. The LEDs ‘charger’ and ‘alarm’ will flash to indicate acceptance of the settings. Page 14 Configuration DS-1 off Charge voltage DS-2 off Charge voltage DS-3 off Charge voltage DS-1 off DS-2 on DS-2 off DS-1 on DS-2 on DS-3 on Example 1: (factory setting) 1.2 GEL 14.4 V 3 Search mode off 3 Store setting: off→ on→ off Example 2 Example 3 1.2 Tubular plate 15V 3 Search mode off 3 Store setting: off→ on→ off 1.2 Gel Victron Long Life Li-ion (LiFePO4) 3 Search mode off 3 Store setting: off→ on→ off